This item has been tested and meets safety standards imposed by the Underwriters Laboratories (UL).
This unit uses energy efficient and long lasting LED's.
This unit contains a battery for backup power. The battery must be connected during installation.
FEATURES
- UL 924, NFPA 70, NFPA 101, CEC 20, and Wet Location Listed
- 120-277VAC 50/60Hz
- Fully sealed and gasketed housing
- Includes 2 Adjustable Lamp Heads
- Maintenance-free NiCad Battery
- Sealed momentary push-to-test switch & AC indicator light
To use with with remote heads, please change the Operation Type above to Battery Backup + Remote Head Capable to ensure compatibility. Code at time of checkout must read: EL-LWET-W-RH.
SPECIFICATIONS
Dimensions | |
---|---|
Height | 11.50" |
Depth | 2.75" |
Length | 10.25" |
Weight | 10.00 lb |
WHAT'S INCLUDED
- Wet Listed Emergency Light
- Installation Instructions & Hardware
- NiCad Battery - Must connect the battery after installation (Located inside unit)
CONSTRUCTION
The EL-LWET Emergency Light is constructed from durable polycarbonate with a waterproof, flame-retardant plastic enclosure and fully rotational lamp heads, ideal for wet locations.
ILLUMINATION
EL-LWET emergency unit uses two top mounted heads lamps with an output of 380lm. Heads are constructed from high impact thermoplastic. Fully-adjustable.
EMERGENCY OPERATION
Upon failure of the normal utility power, an internal solid-state transfer switch automatically provides uninterrupted emergency operation for at least 90 minutes. The fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours.
BATTERY - BATTERY BACKUP
The EL-LWET Emergency Light is designed with a maintenance-free 7.2V 2000mAh NiCad battery that provides a minimum emergency duration of 90 minutes. Recharge time of the battery is 24 hours.
OPERATIONAL TEMPERATURE
Temperature Ratings | |
Series | Temperature |
Standard Option | 32°F to 122°F |
Cold Weather Option | -13°F to 122°F |
PHOTOMETRICS
Total Luminaire Lumens : 380lm
Standard mounting height of 8ft illuminates 1 footcandle (FC) spaced at 45ft for a 3ft path of egress.
Mounting height of 12ft illuminates 1 footcandle (FC) spaced at 40ft for a 3ft path of egress.
Disclosure:
Spacing is measured in lab condition with an assumed open space, no obstruction and reflection rates of 80 (ceiling) / 50 (walls) / 20 (floor). Actual spacing may vary depending on what environment the fixture is installed in.
REMOTE HEAD CAPABLE OPTION
The remote head capability option allows the EL-LWET unit to supply power to up to two additional 6V remote heads up to 3W. The remote heads would then operate on the same emergency mode as the standard units (see Emergency Operation Section).
ELECTRICAL COMPONENTS
The EL-LWET emergency light features a 120-277VAC dual voltage input, a brownout circuit, battery low voltage protection, a solid-state transfer circuit, a test switch with a battery charging indicator, and a maintenance-free Ni-Cad battery that recharges in 24 hours and provides over 90 minutes of discharge time..
INSTALLATION
The EL-LWET is suitable for surface wall mounting, designed with a universal J-Box mounting pattern on back plate.
Mounting Configurations Explained